Mains Failure: 3-attempt engine cranking after mains failure otherwise the engine fails to start. Engine start-up within 10 sec of mains failure otherwise 2 more start pulses after every 10-15 seconds
Unhealthy Mains: Any of the phase failure or voltage drops below set value
Mains Restoration: Engine keeps running for 30 seconds before stopping, as recommended by the Engine manufacturer
Metering One Ammeter with CTs & selector switch, one frequency meter, one voltmeter with selector switch and one hour meter
Set of indications
Load on DG
Load on mains
Fault indications
LLOP
High water temp/high cylinder head temp
Overload
Set of Push Buttons
Engine start/stop
Alarm acknowledge button for hooter
Reset button for fault indication
Safety
High water temperature
Overload trip
Battery Charger: A separate battery charger for continuous charging of batteries in trickle/boost mode to ensure prompt starting of the engine.